Article Description / Summary
HLP1073 a- Using The PID Wizard
< a > b USC Config 106 contains a wizard to create programs for the USC701. These programs are easy to make and enable technicians with no programming experience to create a large variety of signal conditioning modules from just ...
HLP1074 b- Modify PID Wizard Result
a < b > c b- Use the modify wizard to change the input calibration to any special sensor types. The Modify Wizard Select CH1 as shown then press configure. Click the small r button to change the range on channel 1. Select type ...
HLP1075 c- Hot Keys Created With The PID Wizard
b < c > d All the PID wizards define hotkeys for use with the AM702. The keys are defined as the following where appropriate. KEY Description UP Display measurement input DOWN Display setpoint. BACK PID Out% NEXT Display position ...
HLP1076 d- Program USC701 With The PID Wizard
c < d > e Program the USC701 with the initial PID parameters set to: PB (%) = 200 I time S = 50 D time S = 0 Do not program the USC701 while the plant is operating and ensure that the output controller is disabled during the programing ...
HLP1077 e- Create Readings Log For PID Tuning
d < e > f The PID controller can be tuned without using the readings log. Also if the correct or close parameters are known for the plant no tuning is necessary. The readings log screen can chart the last 100 readings while still ...
HLP1078 f- PID Tuning
d < f > Run plant and reduce PB% until control oscillates or increase until control stops oscillating. If the plant has a manual control mode run in manual control and check that the measurement input is reading the correct values. ...